Supply voltage |
AC 115-230V |
Permitted ambient temperature |
-30...+70°C |
Temperature measuring circuits: Type |
1-9 PTC sensors acc. to DIN 44081, DIN 44082 in series |
Temperature measuring circuits: R_25, total |
<1.8kΩ |
Temperature measuring circuits: R_trip |
4.5kΩ ±20% |
Temperature measuring circuits: R_trip, static |
4.5kΩ ±20% |
Temperature measuring circuits: R_reset |
2.75kΩ ±20% |
Temperature measuring circuits: Max. length connection line |
30m |
Resetting the lock |
Main reset >5s only possible if there is no error current |
Relay: Connection |
AC 240V 2.5A C300 at least AC/DC 24V 20mA |
Relay: Mechanical service life |
Approx. 1 million switching cycles |
Protection class acc. To EN 60529 |
IP00 |
Connection type |
Flat plug sleeves (PTC), screw terminals |
Housing material |
PA glass-fibre-reinforced |
Mounting |
Can be snapped onto 35mm standard rail acc. to EN 60715 or screw mounted |
Dimensions |
Refer to dimensions in mm |
Weight |
Approx. 200g |
Check base |
EN 61000-6-2, EN 61000-6-3 EN 61010-1 Overvoltage category II Pollution level 2 |
Approval |
UL File No. E75899 cURus |