Supply voltage |
AC/DC 115-230V |
Permitted ambient temperature |
-30...+70°C |
Temperature measuring circuits: Type |
PTC, accord. to DIN 44081/082 |
Temperature measuring circuits: R_25, total |
<1.8kΩ |
Temperature measuring circuits: R_trip |
11.4kΩ ±20% |
Temperature measuring circuits: R_trip, static |
11.4kΩ ±20% |
Temperature measuring circuits: R_reset |
2.95kΩ ±20% |
Temperature measuring circuits: Max. length connection line |
30m |
Motor voltage |
3 AC 20-100Hz 80-632V ±10% |
Phase monitoring: Phase sequence |
Active about 1s after motor start for about 5s Lock-out shut-off |
Phase monitoring: Phase failure |
Active about 1 second after the motor start until the motor stop Automatic restart after 6min ±1min 3 shut-offs within 12min or 10 shut-offs within 24h leads to a lokked shut-off |
Phase monitoring: Inactive |
10s after motor stop |
Resetting the lock |
Power off >5s |
Relay: Connection |
AC 240V 2.5A C300 AC/DC 24V 20mA |
Relay: Mechanical service life |
Approx. 1 million switching cycles |
Protection class acc. To EN 60529 |
IP00 |
Connection type |
6.3mm flat plug sleeves and screw terminals |
Housing material |
PA glass-fibre-reinforced |
Mounting |
To snap open to 35mm standard rail as under EN 60715 or screw mounting |
Dimensions |
68.4x33x80 (LxWxH) |
Weight |
Approx. 200g |
Check base |
EN 61000-6-2, EN 61000-6-3EN 61010-1 |
Approval |
UL File No. E75899 |